EVOLUTION CONTROLLER

Standard Measurements

  • T-Voltage (R-S, S-T, T-R, R-N, S-N, T-N)
  • Current on all 3 phases
  • Frequency
  • Engine speed indicator
  • Engine cooling temperature
  • Engine oil pressure
  • Battery voltage
  • Alternator battery charger pick up voltage
  • Operating hour counter
  • Starting attempts counter
  • Maintenance countdown

EVOLUTION CONTROLLER

Request a Quotation
  • High Voltage Shutdown Shuts down the generator at >130% rated voltage for 200 milliseconds or >110% for 5 seconds to better protect home owner appliances or connected items.
    Low Voltage Shutdown Shuts down the generator at <60% voltage for 5 seconds to better protect home owners appliances or connected items.
    Internal Fault Shutdown Shuts down the generator when a failure is detected within the Evolution Controller for more protection and easier diagnostics.
    Battery Sentinel Monitors the battery and charging system to indicate that the battery is trending towards failure or that it has failed.
    Event Log All generators 5-13 kVA feature a full event log capable of recording 50 events.
    Smart Battery Charger Only delivers a charge to the battery when needed. Battery charge depends on ambient air temperature.
    Voltage Regulation With the combination into the Evolution Controller, the voltage regulation delivers an industry leading voltage regulation +/- 1%.
    Product Activation Requires each generator to be activated via website or phone before automatic function is enabled - Allows a warranty activation start point for every generator sold.
    External Common Fault Alarm The Evolution Controller has a provision to connect to a set of contacts that will allow for a common alarm when any of the generator shut downs occur- This will allow individuals to connect into security systems, home automation systems or simply drive a different alarm within a home or business.
    Adjustable generator start time When utility fails, the control is factory set to delay 10 seconds prior to starting the engine. There is also the capability to change the delay time between 2-1500 seconds .
    Incorrect Wiring Error Eliminates the potential of damaging the Evolution Controller if it is not connected properly, a warning message is displayed that must be corrected before the controller is allowed to be fully operational.
  • LCD Display
    LED Backlit Membrane Keypad
    Time ∓ Date
    Alarm Log
    Run Log
    Maintenance Log & Reminders
    Set Exercise via Display
    Run Hour Display
    Battery Condition
    Quiet Test Selection